/*  eaton-mib.c - data to monitor Eaton Aphel PDUs (Basic and Complex)
 *
 *  Copyright (C) 2008 - 2010
 *                Arnaud Quette <ArnaudQuette@Eaton.com>
 *
 *  Sponsored by Eaton <http://www.eaton.com>
 *   and MGE Office Protection Systems <http://www.mgeops.com>
 *
 *  This program is free software; you can redistribute it and/or modify
 *  it under the terms of the GNU General Public License as published by
 *  the Free Software Foundation; either version 2 of the License, or
 *  (at your option) any later version.
 *
 *  This program is distributed in the hope that it will be useful,
 *  but WITHOUT ANY WARRANTY; without even the implied warranty of
 *  MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.  See the
 *  GNU General Public License for more details.
 *
 *
 *  You should have received a copy of the GNU General Public License
 *  along with this program; if not, write to the Free Software
 *  Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
 *
 */

#include "eaton-mib.h"

#define EATON_APHEL_MIB_VERSION     "0.45"

/* APHEL-GENESIS-II-MIB (monitored ePDU)
 * *************************************
 * Note: we should also be able to support this one using netxml-ups!
 */

#define APHEL1_OID_MIB                                ".1.3.6.1.4.1.17373"
#define APHEL1_OID_MODEL_NAME                   ".1.3.6.1.4.1.17373.3.1.1.0"
#define APHEL1_OID_FIRMREV                            ".1.3.6.1.4.1.17373.3.1.2.0"
#define APHEL1_OID_DEVICE_NAME                        ".1.3.6.1.4.1.17373.3.1.3.0"
#define APHEL1_OID_UNIT_MACADDR                       ".1.3.6.1.4.1.17373.3.1.4.0"
/* needs concat .<outlet-index>.0 */
#define APHEL1_OID_OUTLET_CURRENT               ".1.3.6.1.4.1.17373.3.2"

/* Snmp2NUT lookup table for GenesisII MIB */
static snmp_info_t eaton_aphel_genesisII_mib[] = {
      /* Device page */
      { "device.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      { "device.model", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_MODEL_NAME,
            "Eaton Powerware ePDU Monitored", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "device.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },

      /* UPS page */
      { "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      { "ups.model", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_MODEL_NAME,
            "Generic SNMP PDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.id", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_DEVICE_NAME,
            "unknown", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_FIRMREV, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      { "ups.macaddr", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_UNIT_MACADDR, "unknown",
            0, NULL, NULL },

      /* Outlet page */
      /* we can't use template since there is no counterpart to outlet.count */
      { "outlet.1.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".1.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.2.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".2.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.3.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".3.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.4.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".4.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.5.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".5.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.6.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".6.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.7.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".7.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
      { "outlet.8.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".8.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },

      /* end of structure. */
      { NULL, 0, 0, NULL, NULL, 0, NULL, NULL }
};


/* APHEL PDU-MIB - Revelation MIB (Managed ePDU)
 * ********************************************* */

#define AR_BASE_OID                             ".1.3.6.1.4.1.534.6.6.6"

#define APHEL2_OID_MODEL_NAME                   AR_OID_MODEL_NAME

#define AR_OID_MODEL_NAME                       AR_BASE_OID ".1.1.12.0"
#define AR_OID_DEVICE_NAME                      AR_BASE_OID ".1.1.13.0"
#define AR_OID_FIRMREV                          AR_BASE_OID ".1.1.1.0"
#define AR_OID_SERIAL                           AR_BASE_OID ".1.1.2.0"
#define AR_OID_UNIT_MACADDR                     AR_BASE_OID ".1.1.6.0"

#define AR_OID_UNIT_CURRENT                     AR_BASE_OID ".1.3.1.1"
#define AR_OID_UNIT_VOLTAGE                     AR_BASE_OID ".1.3.1.2"
#define AR_OID_UNIT_ACTIVEPOWER                 AR_BASE_OID ".1.3.1.3"
#define AR_OID_UNIT_APPARENTPOWER         AR_BASE_OID ".1.3.1.4"
#define AR_OID_UNIT_CPUTEMPERATURE        AR_BASE_OID ".1.3.1.5.0"

#define AR_OID_OUTLET_INDEX                     AR_BASE_OID ".1.2.2.1.1"
#define AR_OID_OUTLET_NAME                      AR_BASE_OID ".1.2.2.1.2"
#define AR_OID_OUTLET_STATUS              AR_BASE_OID ".1.2.2.1.3"

static info_lkp_t outlet_status_info[] = {
      { -1, "error" },
      { 0, "off" },
      { 1, "on" },
      { 2, "cycling" }, /* transitional status */
      { 0, NULL }
};

#define DO_OFF          0
#define DO_ON           1
#define DO_CYCLE  2

#define AR_OID_OUTLET_COUNT                     AR_BASE_OID ".1.2.1.0"
#define AR_OID_OUTLET_CURRENT             AR_BASE_OID ".1.2.2.1.4"
#define AR_OID_OUTLET_MAXCURRENT          AR_BASE_OID ".1.2.2.1.5"
#define AR_OID_OUTLET_VOLTAGE             AR_BASE_OID ".1.2.2.1.6"
#define AR_OID_OUTLET_ACTIVEPOWER         AR_BASE_OID ".1.2.2.1.7"
#define AR_OID_OUTLET_APPARENTPOWER       AR_BASE_OID ".1.2.2.1.8"
#define AR_OID_OUTLET_POWERFACTOR         AR_BASE_OID ".1.2.2.1.9"

/* Snmp2NUT lookup table for Eaton Revelation MIB */
static snmp_info_t eaton_aphel_revelation_mib[] = {
      /* Device page */
      { "device.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      { "device.model", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_MODEL_NAME,
            "Eaton Powerware ePDU Managed", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "device.serial", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_SERIAL, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "device.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },

      /* UPS page */
      { "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      { "ups.model", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_MODEL_NAME,
            "Generic SNMP PDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.id", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_DEVICE_NAME,
            "unknown", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_SERIAL, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_FIRMREV, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL },
      { "ups.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      { "ups.macaddr", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_UNIT_MACADDR, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
      { "ups.temperature", 0, 1, AR_OID_UNIT_CPUTEMPERATURE, NULL, 0, NULL, NULL },

      /* Outlet page */
      { "outlet.id", 0, 1, NULL, "0", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
      { "outlet.desc", ST_FLAG_RW | ST_FLAG_STRING, 20, NULL, "All outlets",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
      { "outlet.count", 0, 1, AR_OID_OUTLET_COUNT, "0", 0, NULL },
      { "outlet.current", 0, 0.001, AR_OID_UNIT_CURRENT ".0", NULL, 0, NULL, NULL },
      { "outlet.voltage", 0, 0.001, AR_OID_UNIT_VOLTAGE ".0", NULL, 0, NULL, NULL },
      { "outlet.realpower", 0, 1.0, AR_OID_UNIT_ACTIVEPOWER ".0", NULL, 0, NULL, NULL },
      { "outlet.power", 0, 1.0, AR_OID_UNIT_APPARENTPOWER ".0", NULL, 0, NULL, NULL },

      /* outlet template definition
       * Caution: the index of the data start at 0, while the name is +1
       * ie outlet.1 => <OID>.0 */
      { "outlet.%i.switchable", 0, 1, AR_OID_OUTLET_INDEX ".%i", "yes", SU_FLAG_STATIC | SU_OUTLET, NULL, NULL },
      { "outlet.%i.id", 0, 1, NULL, "%i", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK | SU_OUTLET, NULL, NULL },
      { "outlet.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_NAME ".%i", NULL, SU_OUTLET, NULL, NULL },
      { "outlet.%i.status", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_STATUS ".%i", NULL, SU_FLAG_OK | SU_OUTLET, &outlet_status_info[0], NULL },
      { "outlet.%i.current", 0, 0.001, AR_OID_OUTLET_CURRENT ".%i", NULL, SU_OUTLET, NULL, NULL },
      { "outlet.%i.current.maximum", 0, 0.001, AR_OID_OUTLET_MAXCURRENT ".%i", NULL, SU_OUTLET, NULL, NULL },
      { "outlet.%i.realpower", 0, 1.0, AR_OID_OUTLET_ACTIVEPOWER ".%i", NULL, SU_OUTLET, NULL, NULL },
      { "outlet.%i.voltage", 0, 1.0, AR_OID_OUTLET_VOLTAGE ".%i", NULL, SU_OUTLET, NULL, NULL },
      { "outlet.%i.powerfactor", 0, 0.01, AR_OID_OUTLET_POWERFACTOR ".%i", NULL, SU_OUTLET, NULL, NULL },
      { "outlet.%i.power", 0, 1.0, AR_OID_OUTLET_APPARENTPOWER ".%i", NULL, SU_OUTLET, NULL, NULL },

      /* FIXME:
       * - delay for startup/shutdown sequence
       * - support for multiple Ambient sensors ( max. 8), starting at index '0'
       *          ambient.%i.temperature => .1.3.6.1.4.1.534.6.6.6.2.2.1.3.%i
       *          ambient.%i.humidity => .1.3.6.1.4.1.534.6.6.6.2.4.1.3.%i
       */

      /* Ambient page */
      /* We use critical levels, for both temperature and humidity,
       * since warning levels are also available! */
      { "ambient.temperature", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.2.1.3.0", NULL, SU_FLAG_OK, NULL, NULL },
      { "ambient.temperature.low", 0, 1.0, "1.3.6.1.4.1.534.6.6.6.2.2.1.6.0", NULL, SU_FLAG_OK, NULL, NULL },
      { "ambient.temperature.high", 0, 1.0, "1.3.6.1.4.1.534.6.6.6.2.2.1.7.0", NULL, SU_FLAG_OK, NULL, NULL },
      { "ambient.humidity", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.4.1.3.0", NULL, SU_FLAG_OK, NULL, NULL },
      { "ambient.humidity.low", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.4.1.6.0", NULL, SU_FLAG_OK, NULL, NULL },
      { "ambient.humidity.high", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.4.1.7.0", NULL, SU_FLAG_OK, NULL, NULL },

      /* instant commands. */
      /* Note that load.cycle might be replaced by / mapped on shutdown.reboot */
      /* no counterpart found!
      { "outlet.load.off", 0, DO_OFF, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL, NULL },
      { "outlet.load.on", 0, DO_ON, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL, NULL },
      { "outlet.load.cycle", 0, DO_CYCLE, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL, NULL }, */
      { "outlet.%i.load.off", 0, DO_OFF, AR_OID_OUTLET_STATUS ".%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL },
      { "outlet.%i.load.on", 0, DO_ON, AR_OID_OUTLET_STATUS ".%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL },
      { "outlet.%i.load.cycle", 0, DO_CYCLE, AR_OID_OUTLET_STATUS ".%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL },

      /* end of structure. */
      { NULL, 0, 0, NULL, NULL, 0, NULL, NULL }
};