Logo Search packages:      
Sourcecode: nut version File versions  Download package

bestpower-mib.c

/*  bestpower-mib.c - data to monitor Eaton Best Power Ferrups
 *                     using earlier version of the ConnectUPS
 *
 *  Copyright (C) 2010 - Arnaud Quette <arnaud.quette@free.fr>
 *
 *  This program is free software; you can redistribute it and/or modify
 *  it under the terms of the GNU General Public License as published by
 *  the Free Software Foundation; either version 2 of the License, or
 *  (at your option) any later version.
 *
 *  This program is distributed in the hope that it will be useful,
 *  but WITHOUT ANY WARRANTY; without even the implied warranty of
 *  MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.  See the
 *  GNU General Public License for more details.
 *
 *
 *  You should have received a copy of the GNU General Public License
 *  along with this program; if not, write to the Free Software
 *  Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
 *
 */

#include "bestpower-mib.h"

#define BESTPOWER_MIB_VERSION       "0.1"
#define BESTPOWER_OID_MODEL_NAME    ".1.3.6.1.4.1.2947.1.1.2.0"

/*
 * http://powerquality.eaton.com/Support/Software-Drivers/Downloads/connectivity-firmware/bestpwr2.mib
 */

static info_lkp_t bestpower_power_status[] = {
      { 1, "OL" },
      { 2, "OB" },
      { 0, "NULL" }
} ;

/* Snmp2NUT lookup table for Best Power MIB */
static snmp_info_t bestpower_mib[] = {
      /* Device page */
      { "device.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "ups",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },

      { "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON",
            SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
      /*.1.3.6.1.4.1.2947.1.1.1.0 = STRING: "Ferrups"
      .1.3.6.1.4.1.2947.1.1.2.0 = STRING: "FE850VA"*/
      { "ups.model", ST_FLAG_STRING, SU_INFOSIZE, BESTPOWER_OID_MODEL_NAME,
            "Best Ferrups", SU_FLAG_STATIC, NULL, NULL },

      { "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.2947.1.1.5.0",
            "", SU_FLAG_STATIC, NULL },
      { "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.2947.1.1.7.0",
            "", SU_FLAG_STATIC,   NULL },
      { "ups.power", 0, 1, ".1.3.6.1.4.1.2947.1.1.3.0", "",
            0, NULL },
      { "ups.mfr.date", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.2947.1.1.8.0", "",
            0, NULL },

      { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.2947.1.2.1.0", "",
            0 /*SU_STATUS_PWR*/, &bestpower_power_status[0] },

      /* Battery runtime is expressed in minutes */
      { "battery.runtime", 0, 60.0, ".1.3.6.1.4.1.2947.1.2.3.0", "",
            0, NULL },
      /* The elapsed time in seconds since the
       * UPS has switched to battery power */
      { "battery.runtime.elapsed", 0, 1.0, ".1.3.6.1.4.1.2947.1.2.2.0", "",
            0, NULL },
      { "battery.voltage", 0, 0.1, ".1.3.6.1.4.1.2947.1.2.4.0", "",
            0, NULL },
      { "battery.current", 0, 0.1, ".1.3.6.1.4.1.2947.1.2.5.0", "",
            0, NULL },

      /* end of structure. */
      { NULL, 0, 0, NULL, NULL, 0, NULL, NULL }
} ;

mib2nut_info_t    bestpower = { "bestpower", BESTPOWER_MIB_VERSION, "",
      BESTPOWER_OID_MODEL_NAME, bestpower_mib };