/*  netvisionmib.h - data to monitor Socomec Sicon UPS equipped 
 *  with Netvision WEB/SNMP card/external box with NUT
 *
 *  Copyright (C) 2004
 *                Thanos Chatziathanassiou <tchatzi@arx.net>
 *
 *  This program is free software; you can redistribute it and/or modify
 *  it under the terms of the GNU General Public License as published by
 *  the Free Software Foundation; either version 2 of the License, or
 *  (at your option) any later version.
 *
 *  This program is distributed in the hope that it will be useful,
 *  but WITHOUT ANY WARRANTY; without even the implied warranty of
 *  MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.  See the
 *  GNU General Public License for more details.
 *
 *
 *  You should have received a copy of the GNU General Public License
 *  along with this program; if not, write to the Free Software
 *  Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
 *
 */

#define NETVISION_MIB_VERSION             "0.1"

/* SNMP OIDs set */
#define NETVISION_OID_UPS_MIB             ".1.3.6.1.4.1.4555.1.1.1.1"
#define NETVISION_OID_UPSIDENTMODEL       ".1.3.6.1.4.1.4555.1.1.1.1.1.1"
#define NETVISION_OID_UPSIDENTFWVERSION         ".1.3.6.1.4.1.4555.1.1.1.1.1.2"
#define NETVISION_OID_UPSIDENTAGENTSWVERSION    ".1.3.6.1.4.1.4555.1.1.1.1.1.3"
#define NETVISION_OID_UPSIDENTUPSSERIALNUMBER   ".1.3.6.1.4.1.4555.1.1.1.1.1.4"

/* UPS Battery */
#define NETVISION_OID_BATTERYSTATUS       ".1.3.6.1.4.1.4555.1.1.1.1.2.1"
info_lkp_t netvision_batt_info[] = {
      { 2, "OL" }, /* battery normal */
      { 3, "LB" }, /* battery low */
      { 4, "LB" }, /* battery depleted */
      { 5, "OB" }, /* battery discharging */
      { 6, "RB" }  /* battery failure */
};

#define NETVISION_OID_SECONDSONBATTERY          ".1.3.6.1.4.1.4555.1.1.1.1.2.2"
#define NETVISION_OID_BATT_RUNTIME_REMAINING    ".1.3.6.1.4.1.4555.1.1.1.1.2.3"
#define NETVISION_OID_BATT_CHARGE         ".1.3.6.1.4.1.4555.1.1.1.1.2.4"
#define NETVISION_OID_BATT_VOLTS          ".1.3.6.1.4.1.4555.1.1.1.1.2.5"

#define NETVISION_OID_INPUT_NUM_LINES           ".1.3.6.1.4.1.4555.1.1.1.1.3.1.0" /* 1phase or 3phase UPS input */
#define NETVISION_OID_OUTPUT_NUM_LINES          ".1.3.6.1.4.1.4555.1.1.1.1.4.3.0" /* 1phase or 3phase UPS output */

/* 
      three phase ups provide input/output/load for each phase 
      in case of one-phase output, only _P1 should be used
*/

#define NETVISION_OID_OUT_VOLTAGE_P1      ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2"
#define NETVISION_OID_OUT_CURRENT_P1      ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3"
#define NETVISION_OID_OUT_LOAD_PCT_P1     ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4"
#define NETVISION_OID_IN_VOLTAGE_P1 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5"

#define NETVISION_OID_OUT_VOLTAGE_P2      ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.2"
#define NETVISION_OID_OUT_CURRENT_P2      ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.2"
#define NETVISION_OID_OUT_LOAD_PCT_P2     ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.2"
#define NETVISION_OID_IN_VOLTAGE_P2 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.2"

#define NETVISION_OID_OUT_VOLTAGE_P3      ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.3"
#define NETVISION_OID_OUT_CURRENT_P3      ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.3"
#define NETVISION_OID_OUT_LOAD_PCT_P3     ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.3"
#define NETVISION_OID_IN_VOLTAGE_P3 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.3"

#define NETVISION_OID_OUTPUT_SOURCE ".1.3.6.1.4.1.4555.1.1.1.1.4.1.0"
info_lkp_t netvision_output_info[] = {
      { 1, "NULL" },   /* output source other   */
      { 2, "NULL" },   /* output source none    */
      { 3, "OL" },     /* output source normal  */
      { 4, "BYPASS" }, /* output source bypass  */
      { 5, "OB" },     /* output source battery */
      { 6, "BOOST" },  /* output source booster */
      { 7, "TRIM" },   /* output source reducer */
      { 8, "NULL" },   /* output source standby */
      { 9, "NULL" },   /* output source ecomode */
};

/* Snmp2NUT lookup table */
snmp_info_t netvision_mib[] = {
      { "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTAGENTSWVERSION, "SOCOMEC SICON UPS",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL },
      { "ups.model", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTMODEL,
            "Generic SNMP UPS", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
      { "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTUPSSERIALNUMBER, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL },
      { "ups.firmware.aux", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTFWVERSION, "",
            SU_FLAG_STATIC | SU_FLAG_OK, NULL },
      { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_BATTERYSTATUS, "",
            SU_FLAG_OK | SU_STATUS_BATT, &netvision_batt_info[0] },
      
      /* ups load */
      { "ups.load", 0, 1, NETVISION_OID_OUT_LOAD_PCT_P1, 0, SU_FLAG_OK, NULL },
      
      /*ups input,output voltage, output frquency phase 1 */
      { "input.voltage", 0, 0.1, NETVISION_OID_IN_VOLTAGE_P1, 0, SU_FLAG_OK, NULL },
      { "output.voltage", 0, 0.1, NETVISION_OID_OUT_VOLTAGE_P1, 0, SU_FLAG_OK, NULL },
      { "output.current", 0, 0.1, NETVISION_OID_OUT_CURRENT_P1, 0, SU_FLAG_OK, NULL },
      
      /* battery info */
      { "battery.charge", 0, 1, NETVISION_OID_BATT_CHARGE, "", SU_FLAG_OK, NULL },
      { "battery.voltage", 0, 0.1, NETVISION_OID_BATT_VOLTS, "", SU_FLAG_OK, NULL },
      { "battery.runtime", 0, 60, NETVISION_OID_BATT_RUNTIME_REMAINING, "", SU_FLAG_OK, NULL },
      
      /* end of structure. */
      { NULL, 0, 0, NULL, NULL, 0, NULL }
};